以保護人身安全為目的,把設(she)備不帶(dai)電的金屬外(wai)殼接(jie)地(di)或接(jie)零,叫做保護接(jie)地(di)及保護接(jie)零。
一、保護接地
在(zai)中性點不接(jie)地的三相系統中,當接(jie)到(dao)這(zhe)個(ge)系統上(shang)的某電(dian)(dian)氣設備因絕(jue)緣損壞(huai)而使外殼帶(dai)電(dian)(dian)時,如果人站在(zai)地上(shang)用手觸及外殼,由于輸電(dian)(dian)線與(yu)地之間有(you)(you)分(fen)布存在(zai),將有(you)(you)電(dian)(dian)流通過人體及分(fen)布電(dian)(dian)容回(hui)到(dao)電(dian)(dian)源(yuan),使人觸電(dian)(dian),如圖(tu)1所示(shi)。在(zai)一般情況下這(zhe)個(ge)電(dian)(dian)流是不大(da)的。但是,如果電(dian)(dian)網分(fen)布很廣,或者電(dian)(dian)網絕(jue)緣強度顯著(zhu)下降,這(zhe)個(ge)電(dian)(dian)流可能(neng)達到(dao)危(wei)險程度 ,這(zhe)就必須(xu)采取(qu)安全措施(shi)。
圖1沒有保護接地的一相碰(peng)殼情況
保(bao)護接地(di)(di)(di)就是(shi)把電(dian)(dian)(dian)氣設(she)備的(de)金屬外(wai)(wai)殼(ke)用足(zu)夠粗的(de)金屬導(dao)線與大地(di)(di)(di)可(ke)靠地(di)(di)(di)連接起來(lai)。電(dian)(dian)(dian)氣設(she)備采用保(bao)護接地(di)(di)(di)措施后,設(she)備外(wai)(wai)殼(ke)已通過導(dao)線與大地(di)(di)(di)有(you)良好的(de)接觸,則當(dang)人體觸及帶電(dian)(dian)(dian)的(de)外(wai)(wai)殼(ke)時,人體相當(dang)于接地(di)(di)(di)電(dian)(dian)(dian)阻(zu)的(de)一(yi)條(tiao)并(bing)聯(lian)支路,如圖2所(suo)示。由(you)于人體電(dian)(dian)(dian)阻(zu)遠遠大于接地(di)(di)(di)電(dian)(dian)(dian)阻(zu),所(suo)以通過人體的(de)電(dian)(dian)(dian)流很小,避免了觸電(dian)(dian)(dian)事故(gu)。
圖2裝有(you)保護接(jie)地(di)的電(dian)動機一(yi)相碰(peng)殼情況
保(bao)護接地應用(yong)于中性點(dian)不接地的配(pei)電系統中。
二、保護接零
(一(yi))保(bao)護接零的概念(nian)
所(suo)謂保(bao)護(hu)接零(ling)(又稱接零(ling)保(bao)護(hu))就是在中(zhong)性點接地的(de)系統(tong)中(zhong),將電(dian)(dian)氣設備在正常情況下不帶電(dian)(dian)的(de)金屬部分(fen)與(yu)零(ling)線作良(liang)好的(de)金屬連接。圖(tu)3是采(cai)用(yong)(yong)保(bao)護(hu)接零(ling)情況下故障電(dian)(dian)流的(de) 示意(yi)圖(tu)。當某一相絕緣損壞使相線碰殼,外殼帶電(dian)(dian)時,由(you)于(yu)外殼采(cai)用(yong)(yong)了保(bao)護(hu)接零(ling)措施,因此該相線和零(ling)線構成回路,單相短(duan)路電(dian)(dian)流很大,足以使線路上的(de)保(bao)護(hu)裝置(zhi)(如熔斷(duan)(duan)器(qi))迅速熔斷(duan)(duan),從而將漏電(dian)(dian)設備與(yu)電(dian)(dian)源斷(duan)(duan)開,從而避免人身觸電(dian)(dian)的(de)可能性。
圖3保護接零
保護接零用于(yu)380/220v、三相四線制、電源的(de)中(zhong)性點(dian)直接接地的(de)配電系統(tong)。
在電(dian)源(yuan)(yuan)的(de)中性點(dian)接(jie)(jie)地(di)(di)的(de)配電(dian)系統中,只能采(cai)用保護接(jie)(jie)零,如果(guo)采(cai)用保護接(jie)(jie)地(di)(di)則不能有效(xiao)地(di)(di)防止人身觸電(dian)事故。如圖4所示,若采(cai)用保護接(jie)(jie)地(di)(di),電(dian)源(yuan)(yuan)中性點(dian)接(jie)(jie)地(di)(di)電(dian)阻(zu)(zu)與電(dian)氣(qi)設(she)備的(de)接(jie)(jie)地(di)(di)電(dian)阻(zu)(zu)均(jun)按4ω考慮,而電(dian)源(yuan)(yuan)電(dian)壓為(wei)220v,那么當(dang)電(dian)氣(qi)設(she)備的(de)絕緣損壞使電(dian)氣(qi)設(she)備外殼(ke)帶電(dian)時,則兩(liang)接(jie)(jie)地(di)(di)電(dian)阻(zu)(zu)間的(de)電(dian)流將為(wei):
圖4中(zhong)性(xing)點接地系統采用保護接地的后果
熔(rong)(rong)斷器熔(rong)(rong)體的(de)額(e)定電(dian)(dian)流是根據被保護設備的(de)要求選定的(de),如果(guo)設備的(de)容易較大,為(wei)(wei)了保證設備在(zai)正常情(qing)況下(xia)工作,所選用(yong)熔(rong)(rong)體的(de)額(e)定電(dian)(dian)流也會(hui)較大,在(zai)27.5a接地短路電(dian)(dian)流的(de)作用(yong)下(xia),將不斷熔(rong)(rong)斷,外(wai)(wai)殼帶電(dian)(dian)的(de)電(dian)(dian)氣設備不能立即(ji)脫離電(dian)(dian)源,所以(yi)在(zai)設備的(de)外(wai)(wai)殼上長期存在(zai)對地電(dian)(dian)壓(ya)ud,其(qi)值為(wei)(wei)
ud=27.5×4 = 110v
顯(xian)然(ran),這(zhe)是很危(wei)險(xian)的(de)。如(ru)果保護接地電(dian)(dian)(dian)阻大于電(dian)(dian)(dian)源中性點接地電(dian)(dian)(dian)阻,設備外殼(ke)的(de)對地電(dian)(dian)(dian)壓還要(yao)高,這(zhe)時危(wei)險(xian)更大。
三(san)、保護接(jie)零和保護接(jie)地的適用范圍
對于以下電(dian)氣設備的金屬部分均應采取保(bao)(bao)護接零或保(bao)(bao)護接地措施。
1、電機、變壓(ya)器、電器、照(zhao)明(ming)器具、攜帶式(shi)及移動(dong)式(shi)用電器具等的(de)底座和外殼;
2、電氣設備的傳(chuan)動裝置(zhi);
3、電(dian)壓(ya)和電(dian)流的二次(ci)繞(rao)阻;
4、配(pei)電(dian)屏與控制屏的框架;
5、室內、外配電(dian)裝置的金(jin)屬架、鋼筋(jin)混凝土的主筋(jin)和(he)金(jin)屬圍欄;
6、穿線的鋼(gang)管、金(jin)屬接線盒和電(dian)纜(lan)頭、盒的外(wai)殼;
7、裝有避(bi)雷(lei)線(xian)的線(xian)路(lu)的桿塔和裝在配電線(xian)路(lu)電桿上(shang)的開(kai)關設備(bei)及的外殼。
- 上一篇:什么是功率因數?及提高功率因數方法